| Model Type |
IMPERIAL |
|
| Model Name |
IMD-1025U |
|
|
AC INPUT
|
|
| AC Input Capacity on Battery |
1025VA |
|
| AC Input Voltage |
100V or 110V/115V/120V or 220V/230V/240V +/- 25% at line input |
|
| AC Input Frequency |
50 or 60 Hz +/- 10% (auto sensing) |
|
|
AC OUTPUT
|
|
| AC Output Voltage |
Simulated sine wave at 100V or 110V/115V/120V or 220V/230V/240V +/- 5% |
|
| AC Output Frequency |
50 or 60 Hz +/- 1Hz |
|
| AC Output Voltage Regulation |
AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal |
|
| AC Output Transfer |
2/4 milliseconds, including detection time |
|
|
PROTECTION
|
|
| Protection Spike |
1050 Joules (max.) |
|
| Protection Overload |
UPS automatic power off if overload exceeds 110% of nominal at 60 seconds and 130% at 3 seconds |
|
| Protection Inside Protection |
UPS output cut off immediately or input circuit breaker protection |
|
|
BATTERY
|
|
| Battery Type |
Sealed, maintenance-free lead acid |
|
| Battery Typical |
6 hours (to 90% of full capacity) |
|
| Battery Protection |
Auto discharge protection |
|
| Battery Run Time |
50 min |
|
|
PHYSICAL
|
|
| Physical Weight kgs |
13.4 |
|
| Physical Weight lbs |
28.6 |
|
| Physical Shipping Weight kgs |
14.8 |
|
| Physical Shipping Weight lbs |
32.6 |
|
| Physical Dimension mm |
130x382x192 |
|
| Physical Dimension inch |
5.1x15.0x7.6 |
|
| Physical Receptacles |
NEMA 5-15R (battery: 4, Bypass: 2) |
|
|
|
|
ALARM
|
|
| Alarm Battery Backup |
Slow beeping sound (about 0.47 Hz) |
|
| Alarm Battery Low |
rapid beeping sound (about 1.824 Hz) |
|
| Alarm Overload |
Continously beeping sound |
|
|
INTERFACE
|
|
| Interface Option |
USB |
|
|